BRITISH STANDARD
Code of practice for the operation of fire protection measures
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
Part 3: Electrical actuation of pre-action sprinkler systems
ICS 13.220.20
NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
BS 7273-3:2000
BS 7273-3:2000
Committees responsible for this British Standard The preparation of this British Standard was entrusted by Technical Committee FSH/12, Fire detection and alarm systems, to Subcommittee FSH/12/4, Automatic operation of fire protection, upon which the following bodies were represented:
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
British Fire Protection Systems Association British Telecommunications plc Department of the Environment, Transport and the Regions (Building Research Establishment) Home Office Institute of Fire Safety London Fire and Civil Defence Authority Loss Prevention Council Ministry of Defence
This British Standard, having been prepared under the direction of the Health and Environment Sector Committee, was published under the authority of the Standards Committee and comes into effect on 15 October 2000 BSI 10-2000
Amendments issued since publication Amd. No.
The following BSI references relate to the work on this standard: Committee reference FSH/12/4 Draft for comment 99/540022 DC ISBN 0 580 33185 7
Date
Comments
BS 7273-3:2000
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
Contents Page Committees responsible Inside front cover Foreword ii Introduction 1 1 Scope 2 2 Normative references 2 3 and definitions 3 4 System design 3 5 Fire detection 4 6 System interface 4 7 Power supplies 6 8 Wiring 7 9 Servicing 7 Annex A (informative) Example of an arrangement for separate fire alarm and pre-action control and indicating equipment 8 Annex B (informative) Example of an arrangement for fire detectors and pre-action valve-set connected to and monitored by a single control 9 Annex C (informative) Example of an arrangement for any coincidence logic provided at fire alarm control and indicating equipment 10 Annex D (informative) Example of an arrangement for any coincidence logic provided at pre-action control and indicating equipment 11 Figure 1 Ð Typical logic gate depiction of pre-action systems 2 Figure A.1 Ð Example of an arrangement for separate fire alarm and pre-action control and indicating equipment 8 Figure B.1 Ð Example of an arrangement for fire detectors and pre-action valve-set connected to and monitored by a single control 9 Figure C.1 Ð Example of an arrangement for any coincidence logic provided at fire alarm control and indicating equipment 10 Figure D.1 Ð Example of an arrangement for any coincidence logic provided at pre-action control and indicating equipment 11 Table 1 Ð Maximum areas of coverage per point-type smoke detector to operate pre-action sprinkler installations in still air conditions for coincidence and non-coincidence connection fire detection systems 4
BSI 10-2000
i
BS 7273-3:2000
Foreword This British Standard code of practice has been prepared by Technical Committee FSH/12. It is part of a series of standards covering the actuation of fire protection measures. BS 7273-1 and BS 7273-2 cover the electrical and mechanical actuation of gaseous extinguishing systems, BS 7273-3 is concerned with the ªprimingº of pre-action systems, i.e. the rapid conversion of what is essentially a dry pipe sprinkler system into a wet pipe system. This code of practice takes into current British and Eurpean Standards for fire detection systems (see BS 5445, BS 5839 and BS EN 54) and for sprinkler systems (see BS 5306-2). Annexes A, B, C and D are informative. As a code of practice, this British Standard takes the form of guidance and recommendations. It should not be quoted as if it were a specificaiton and particular care should be taken to ensure that claims of compliance are not misleading. NOTE It has been assumed in the drafting of this British Standard that the execution of its provisions is entrusted to appropriately qualified and competent people.
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
A British Standard does not purport to include all the necessary provisions of a contract. s of British Standards are responsible for their correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations.
Summary of pages This document comprises a front cover, an inside front cover, pages i and ii, pages 1 to 11 and a back cover. The BSI copyright notice displayed in this document indicates when the document was last issued.
ii
BSI 10-2000
BS 7273-3:2000
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
Introduction A pre-action sprinkler system consists of a sprinkler system and an electrical detection system with water held back by the pre-action valve and pressurized air in the sprinkler pipework. In the event of the operation of the electrical detection system the pre-action valve operates and allows water into the sprinkler pipework. Two generic forms of operation exist: the ªtype 1º pre-action system and the ªtype 2º pre-action system. The type 1 pre-action system will only discharge water onto the seat of the fire when both the electrical detection system and a sprinkler or sprinklers have operated. Water will only enter the sprinkler pipework following the pre-arranged operation of the detection system. Any accidental damage to the sprinklers or pipework will not cause water to be discharged. The type 1 systems are, therefore, normally used in situations in which: Ð there is high potential for mechanical damage to the system; or Ð the probability of mechanical damage may not be high, but the consequences of inadvertent water damage would include serious damage to sensitive contents and/or major interruption to business. The type 2 pre-action system will discharge water onto the seat of a fire when a sprinkler or sprinklers operate, whether or not the electrical detection system has operated. However, normally the fire detection system will operate before a sprinkler head so that, in effect, the system is ªwetº at the time of sprinkler operation. The type 2 systems are normally used in circumstances in which there is a need to speed up the operation of a dry system. The functions of the two systems can be depicted by the binary logic sequence using ªandº and ªorº gates as given in Figure 1. It is of extreme importance that fire detection systems and any interfaces associated with preaction sprinkler systems have high integrity and do not cause the pre-action valve to remain closed under fire conditions. The seriousness of this circumstance cannot be overstated. It is also important to avoid inadvertent operation of the pre-action valve, as draining down of the system may be time consuming and inconvenient. The recommendations in this code of practice take these factors into , as well as the recommendations of the relevant British and European Standards covering fire detection (BS 5445, BS 5839 and BS EN 54) and sprinklers (BS 5306-2).
BSI 10-2000
1
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
BS 7273-3:2000
Figure 1 Ð Typical logic gate depiction of pre-action systems
1 Scope This part of BS 7273 gives recommendations for the design, installation, operation and servicing of electrical equipment used for the actuation of pre-action sprinkler systems.
2 Normative references The following normative documents contain provisions which, through reference in this text, constitute provisions of this part of this British Standard. For dated references, subsequent amendments to, or revisions of, any of these publications do not apply. For undated references, the latest edition of the publication referred to applies. BS 5306-2, Fire extinguishing installations and equipment on premises Ð Part 2: Specification for sprinkler systems. BS 5445 (all parts), Components of automatic fire detection systems. BS 5839-1:1988, Fire detection and alarm systems for buildings Ð Part 1: Code of practice for system design, installation and servicing. BS 5839-5, Fire detection and alarm systems for buildings Ð Part 5: Specification for optical beam smoke detectors. BS 6266, Code of practice for fire protection for electronic data processing installations. BS 7671, Requirements for electrical installations Ð IEE Wiring Regulations Ð Sixteenth edition. BS EN 54-2, Fire detection and fire alarm systems Ð Part 2: Control and indicating equipment. BS EN 54-4, Fire detection and fire alarm systems Ð Part 4: Power supply equipment. BS EN 60651, Specification for sound level meters. 2
BSI 10-2000
BS 7273-3:2000
3 and definitions For the purposes of this part of BS 7273, the following and definitions apply. 3.1 pre-action system dry, or alternate in dry mode, sprinkler installation in which the alarm valve can be opened by an independent fire detection system in the protected area 3.2 coincidence connection facility provided in a fire detection system so that an output is obtained only when at least two independent detection inputs are present at the same time
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
4 System design 4.1 General considerations The pre-action mode of operation introduces considerable additional complexity over and above the relatively simple mechanical engineering associated with a standard sprinkler installation conforming to BS 5306-2. Inevitably this affects the reliability of the system, although one of the main functions of this code of practice is to ensure that reliability is maximized. Before a type 1 pre-action system is specified, it should be confirmed that the justification of use of a pre-action system outweighs the additional risk that the system will fail to operate correctly in the event of fire. 4.2 Zoning of the pre-action sprinkler system Zoning of pre-action sprinkler systems should be in accordance with the requirements and recommendations of BS 5306-2. 4.3 Inter-relationship between detection system zoning and sprinkler system zoning Each pre-action sprinkler installation requires a detection system to operate the pre-action valve when the appropriate detection inputs are received. Where single compartments are protected by more than one pre-action sprinkler installation, each sprinkler installation should be regarded as a zone of protection. In such instances consideration should be given to a fire occurring between, or on the borders of two or more zones. In this event the detection system(s) should open all of the pre-action valves providing protection for that compartment. 4.4 Manual operation 4.4.1 Both type 1 and type 2 systems should have a dedicated facility for manual initiation of system charging. This may interface with the pre-action system via the associated automatic fire detection system, but should be additional to any arrangement whereby operation of a fire alarm call point results in charging of the system. NOTE Recommendations for manual release switches are given in 6.6.1.
4.4.2 The activation of a manual release switch should charge the sprinkler installation system immediately. 4.4.3 Manual release switches should be sited at a strategic location(s) where they are readily accessible in an emergency. This should include a manual release switch at the control . 4.4.4 When more than one pre-action sprinkler installation is protecting an area and only one system is to be charged with water, it is essential that care is taken in identifying the manual release switch for each system to ensure the correct system is charged with water. 4.4.5 If a single fire compartment is protected by more than one pre-action sprinkler installation, the manual release switches may be grouped or linked together. 4.4.6 It is not normal practice to use fire alarm manual call points to activate the pre-action system. However, according to the application of the system and the associated risks, manual call points may be used to contribute to the activation in conjunction with fire detectors, or may be used to directly initiate activation. 4.5 Automatic operation 4.5.1 Systems should normally be charged by the operation of more than one automatic fire detector. The fastest response for charging a pre-action sprinkler system is obtained from a signal from a single detector. However, where the potential for false alarms and the resultant need to drain the system is unacceptable, a coincidence arrangement should be used. BSI 10-2000
3
BS 7273-3:2000
It should be appreciated that the response time is increased when coincidence connection is used. Any benefits or disadvantages from early filling of the sprinkler pipework should be considered at the design stage. Where coincidence detection is used, the recommendations of Table 1 and where appropriate, BS 6266, should be followed. 4.5.2 Detectors should conform to the relevant parts of BS 5445 or to BS 5839-5. They should be installed in accordance with Table 1 and the recommendations of BS 5839-1 and, where appropriate, BS 6266. Table 1 Ð Maximum areas of coverage per point-type smoke detector to operate preaction sprinkler installations in still air conditions for coincidence and noncoincidence connection fire detection systems
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
Hazard
Maximum area of coverage per detector One (non-coincidence connection) detector
Two (coincidence connection) detectors
m2
m2
Light 100 Ordinary groups I, II and III 100 Ordinary groups III storage and III 50 special High process and storage 50 categories I, II, III and IV
50 50 25 25
NOTE Occupancies, where a fast response is essential or those having electronic data processing (EDP) installations, may require areas of coverage per detector smaller than those stated in the table. Appropriate values for EDP installations are given in BS 5839-1 and/or BS 6266, as appropriate.
Where the hazard category of the sprinkler system is high [OH III and higher (see BS 53062)] consideration should be given to increasing the density of detectors. In the case of protected areas with forced ventilation providing more than four air changes per hour, the area of detector coverage should be reduced to 15 m2 per detector, unless the forced ventilation is stopped on operation of any one detector, in which case a coverage of 25 m2 per detector should be used. Ventilation systems should be shut down on detection of fire.
5 Fire detection The type(s) of detector selected should conform to the recommendations of BS 5839-1 and, where appropriate, those of BS 6266. Point smoke detectors are normally used to initiate charging of the sprinkler pipework. Very high sensitivity fire detection systems, such as many aspirating type systems, should not normally be used in view of the higher potential for false alarms associated with such systems. NOTE If other types of detector (heat, flame) are used, careful consideration should be given to the effect on response time.
6 System interface 6.1 General The automatic fire detectors associated with the pre-action sprinkler installation(s) should be arranged in one of the following two ways. a) Automatic fire detectors may be connected to, and monitored by, dedicated fire alarm control and indicating equipment that does not form part of the control and monitoring facilities for the pre-action valves, e.g. the fire detection may form part of the general fire detection and alarm system in the building (see annex A). When the general fire detection system is to be used as the detection system for the preaction system, separate detection zones should be allocated to the area protected by the preaction system, so that it is clear that the fire alarm indication is from the area protected by the pre-action system and not an adjacent area or another part of the building. b) Automatic fire detectors may be connected to the control and indicating equipment which is dedicated to the pre-action sprinkler installation and which controls and monitors the pre-action valves as well as monitoring the fire detectors (see annex B).
4
BSI 10-2000
BS 7273-3:2000
In the case of a), a facility is needed for transmission of a signal(s) from the fire detection and alarm system control and indicating equipment to separate pre-action sprinkler system control and indicating equipment. All connections between the two control s and to any normally closed solenoid valves should be monitored. NOTE 1 The transmission facility may, for example, comprise a volt free , switched 24 V supply or any other arrangement with similar integrity and reliability.
In the case of b), fire alarm signals should be transmitted from the pre-action control and indicating equipment to the building's fire alarm control and indicating equipment. Any such transmission path should be monitored. In either case a) or b), any fault which would prevent charging of the pre-action sprinkler system in the event of fire should, within 100 s of its occurrence, initiate charging of the preaction system. If the sprinkler installation is to be charged only when, for example, two independent fire detectors have operated, the coincidence logic should be provided at either the fire alarm control and indicating equipment (see annex C), or at the pre-action control and indicating equipment (see annex D).
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
NOTE 2 Other arrangements may also be used.
6.2 Interface design In the case of the arrangement shown in Figure A.1, the fire alarm control and indicating equipment should conform to the requirements of BS EN 54-2 and BS EN 54-4. In the absence of a specification for control equipment for pre-action sprinkler systems, the design and manufacture of the pre-action control and indicating equipment in the arrangement shown in Figures A.1 and B.1 should be in accordance with the specifications for fire detection and alarm system control and indicating equipment in BS EN 54-2 and BS EN 54-4. Whichever arrangement is adopted, no single component failure or failure of a processor to correctly execute its function should prevent the charging of the pre-action sprinkler system. NOTE This recommendation can be satisfied by duplication of components (or other redundancy in circuit design), by an arrangement in which a fault results in charging of the pre-action sprinkler system, or by a combination of the two. Where the above recommendation is achieved either partly or wholly by duplication of components, a failure of any one of the duplicated components should result in a fault warning (but not necessarily charging of the sprinkler system).
6.3 Visual and audible indication at the control equipment In the case of the arrangement in Figure A.1, the pre-action control and indicating equipment should incorporate all visual and audible indicating facilities specified in BS EN 54-2, other than those associated with fire detection circuits. In the case of the arrangement in Figure B.1, the pre-action control and indicating equipment should incorporate all visual and audible indicating facilities specified in BS EN 54-2. In both Figure A.1 and Figure B.1, the pre-action control and indicating equipment should be provided with facilities for visual indication of each of the following conditions: a) power supply healthy; b) system fault (as defined by the relevant clauses of BS EN 54-2); c) system disabled (e.g. by use of any control provided to isolate automatic detectors or the release mechanism); d) low air pressure; e) system failed to charge; f) system charged. A control sounder within or external to the system control equipment should give an audible warning in the event of conditions listed in b) to e). The audible fire and fault warning sounders should each produce a sound level of at least 50 dBA at every point less than 1 m from the control equipment enclosure when measured with an instrument conforming to BS EN 60651. The system charged indication should be derived from a pressure switch in the sprinkler installation pipework. Any sprinkler zone should be separately identifiable at the controls as a detection zone.
BSI 10-2000
5
BS 7273-3:2000
6.4 Output signals from control equipment The pre-action system interface equipment should be provided with the following outputs: a) output(s) for connection of two solenoid valves or actuator mechanisms arranged so that a single open circuit or short circuit at any point on the external wiring will not prevent both solenoid valves or actuation mechanisms from operating; NOTE 1 This recommendation can be met either by the provision of two independent circuits to the solenoid valves or actuator devices, or by a single output to a ring circuit that includes protection against both open circuit and short circuit faults.
b) outputs to any audible warning devices required for indication of fire; NOTE 2 Where the purpose of these outputs is to provide the primary warning of fire to occupants of the building, two independent outputs should be provided to enable conformity to BS 5839-1. Where coincidence detection is used, such outputs may operate on the first or second input, as appropriate.
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
c) outputs for system fault, system charged, system failed to charge. 6.5 Monitoring All external input and output circuits, including any connections to fire alarm control and indicating equipment and to any normally closed solenoid valves, should be monitored in accordance with BS 5839-1, BS EN 54-2 and BS EN 54-4. An open or short circuit on any input to the pre-action interface equipment and to and from the fire alarm control and indicating equipment should result in a fault indication at the pre-action interface equipment. 6.6 Control and indicating devices 6.6.1 Manual release Where a manual release switch is provided, its operation should result in the following: a) a silenceable audible warning; b) operation of the release mechanism to open the pre-action sprinkler system control valve; c) a latched visual indication. Operation of an electrical manual release should require two actions (e.g. lifting a flap and breaking a frangible element, or lifting a flap and operating a key switch) to prevent accidental operation. The manual release housing should be predominantly yellow in colour and marked with operating instructions. Switches that require the breaking of a glazed cover in order to reach the manual release should be avoided because of the potential hazard to the operator. 6.6.2 Filling of pipework The filling of pipework resulting from the operation of the release mechanism should produce the following: a) a silenceable audible warning; b) a latched visual indication at the control and indicating equipment; c) a system charged indication. NOTE Failure of a system to charge on demand (i.e. a short time after transmission of a signal to the release mechanism) should result in a dedicated visual and audible indication.
6.6.3 Remote signalling Confirmation of any operation of the pre-action sprinkler system should be derived from a pressure or flow switch in the discharge pipework, and not from the actuating signal output of the pre-action control equipment. Any signal should be transmitted to the main fire control equipment. Consideration should be given to the need for delay timers to be used in conjunction with the flow switches to avoid unwanted alarms.
7 Power supplies The power supplies for the fire detection and alarm system and the pre-action sprinkler system should be in accordance with BS 5839-1, with an isolating protective device labelled ªFIRE EXTINGUISHING SYSTEM: DO NOT SWITCH OFFº. NOTE A common power supply for the pre-action system and the detection and alarm system may be used provided that there is no adverse interaction between them and that there is sufficient capacity in the standby supplies to meet simultaneously the maximum load requirement for both systems. The standby capacity for the system should be determined against the system requirements when considering BS 58391:1988, 16.5.2.2 for supervised systems and BS 5839-1:1988, 16.5.2.3 for other systems.
6
BSI 10-2000
BS 7273-3:2000
8 Wiring The wiring of the pre-action sprinkler system should have a fire resistance recommended by BS 5839-1 for applications requiring prolonged operation during a fire. All wiring should be installed to satisfy the recommendations of BS 5839-1 and BS 7671, published by the Institution of Electrical Engineers1).
9 Servicing 9.1.1 The of the installation should ensure that the system is in good working order at all times. NOTE This can be achieved by entering into an ªinspection and serviceº contract whereby the manufacturer, his/her agent or an accredited servicing organization carries out this inspection.
9.1.2 The should undertake responsibility for daily and weekly attention in accordance with the manufacturer's/installer's recommendations and with BS 5839-1 and BS 5306-2. Appropriate levels of care should be exercised when operating or checking the system. Training should normally be given by the manufacturer or his/her agent.
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
9.1.3 The fire detection and alarm system should be inspected and tested, serviced and maintained in accordance with BS 5839-1. The pre-action sprinkler system should be tested, serviced and maintained in accordance with BS 5306-2. Records of all inspections and tests should be maintained. 9.1.4 The operation of any remote connections, ancillary operating devices and sounders should be tested during the quarterly visit for the fire detection and alarm system maintenance (as specified in BS 5839-1).
1) BS 7671, Requirements for electrical installations, IEE Wiring Regulations, Sixteenth edition. Available from Station House, Nightingale Rd, Hitchin, Herts.
BSI 10-2000
7
BS 7273-3:2000
Annex A (informative) Example of an arrangement for separate fire alarm and pre-action control and indicating equipment
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
Figure A.1 shows an example of an arrangement for separate fire alarm and pre-action control and indicating equipment.
Figure A.1 Ð Example of an arrangement for separate fire alarm and pre-action control and indicating equipment
8
BSI 10-2000
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
BSI 10-2000
Annex B (informative) Example of an arrangement for fire detectors and pre-action valve-set connected to and monitpred by a single control Figure B.1 shows an example of an arrangement for fire detectors and pre-action valve-set connected to and monitored by a single control .
9
BS 7273-3:2000
Figure B.1 Ð Example of an arrangemrent for fire detectors and pre-action valve-set conneted to and monitored by a single control
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
Figure C.1 Ð Example of an arrangement for any coincidence logic provided at fire alarm control and indicating equipment
BS 7273-3:2000
10
Annex C (informative) Example of an arrangement for any coincidence logic provided at fire alarm control and indicating equipment Figure C.1 shows an example of an arrangement for any coincidence logic provided at fire alarm control and indicating equipment.
BSI 10-2000
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
BSI 10-2000
Annex D (informative) Example of an arrangement for any coincidence logic provided at pre-action control and indicating equipment Figure D.1 shows an example of an arrangement for any coincidence logic provided at pre-action control and indicating equipment.
11
BS 7273-3:2000
Figure D.1 Example of an arrangement for any coincidence logic provided at pre-action control and indicating equipment
Licensed copy:Merseyside Fire, 07/12/2005, Uncontrolled Copy, © BSI
BS 7273-3:2000
BSI 389 Chiswick High Road London W4 4AL
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
BSI Ð British Standards Institution BSI is the independent national body responsible for preparing British Standards. It presents the UK view on standards in Europe and at the international level. It is incorporated by Royal Charter. Revisions British Standards are updated by amendment or revision. s of British Standards should make sure that they possess the latest amendments or editions. It is the constant aim of BSI to improve the quality of our products and services. We would be grateful if anyone finding an inaccuracy or ambiguity while using this British Standard would inform the Secretary of the technical committee responsible, the identity of which can be found on the inside front cover. Tel: 020 8996 9000. Fax: 020 8996 7400. BSI offers an individual updating service called PLUS which ensures that subscribers automatically receive the latest editions of standards. Buying standards Orders for all BSI, international and foreign standards publications should be addressed to Customer Services. Tel: 020 8996 9001. Fax: 020 8996 7001. In response to orders for international standards, it is BSI policy to supply the BSI implementation of those that have been published as British Standards, unless otherwise requested. Information on standards BSI provides a wide range of information on national, European and international standards through its Library and its Technical Help to Exporters Service. Various BSI electronic information services are also available which give details on all its products and services. the Information Centre. Tel: 020 8996 7111. Fax: 020 8996 7048. Subscribing of BSI are kept up to date with standards developments and receive substantial discounts on the purchase price of standards. For details of these and other benefits hip istration. Tel: 020 8996 7002. Fax: 020 8996 7001. Copyright Copyright subsists in all BSI publications. BSI also holds the copyright, in the UK, of the publications of the international standardization bodies. Except as permitted under the Copyright, Designs and Patents Act 1988 no extract may be reproduced, stored in a retrieval system or transmitted in any form or by any means ± electronic, photocopying, recording or otherwise ± without prior written permission from BSI. This does not preclude the free use, in the course of implementing the standard, of necessary details such as symbols, and size, type or grade designations. If these details are to be used for any other purpose than implementation then the prior written permission of BSI must be obtained. If permission is granted, the may include royalty payments or a licensing agreement. Details and advice can be obtained from the Copyright Manager. Tel: 020 8996 7070.